Static Pressure Calculator

Add up the total external static pressure from filter, coil, duct, and register losses

Frequently Asked Questions

What is total external static pressure (TESP)?

TESP = sum of pressure drops across filter + coil + supply duct + return duct + grilles/registers, in inches of water column. Manufacturer-rated TESP is typically 0.5 in w.c. for residential PSC blowers, 0.8 in w.c. for ECM.

What are typical drops by component?

High-MERV filter: 0.15–0.30 in. Wet evaporator coil: 0.20–0.30 in. Supply duct: 0.10–0.20 in. Return: 0.10 in. Registers/grilles: 0.03–0.05 in each. Add a 0.10 in safety margin.

How do I measure it on a running system?

Drill ¼ in test ports before the air handler return and after the supply plenum (downstream of coil); measure with a manometer. TESP = supply reading − return reading (absolute values added).

What happens if TESP exceeds the rating?

Airflow collapses - a 1,200 CFM blower at 0.5 in rated may deliver only 800 CFM at 0.9 in. Coils freeze, capacity drops, and ECM motors run hotter and shorten life.

Important Disclaimer: Estimates for informational purposes only.

This calculator provides estimates for informational purposes only. Results are based on assumptions and may not reflect actual outcomes. Consult qualified professionals in relevant fields before making important decisions based on these results.